N SPIRAL FIRE PROTECTION NOZZLES

FM and UL Approved Full Cone Nozzles for Offshore Fire Protection
Detail Full Cone Spray Pattern Icon

DESIGN FEATURES

Designed specifically with critical fire and explosion suppression applications in mind

One-piece, no internal parts

Clog-resistant

Rugged, compact design

Optional protective cover

All N1-N3W nozzles provided with integral strainer

N1-N3W strainer: 316 SS, 24 mesh (0.027" opening)

Factory Mutual (FM) and U.S. Coast Guard approved models; UL listed


HOW SPRAY PATTERN IS ACHIEVED

The spray pattern of the spiral nozzle is formed by the fluid shearing along with the turns of the spiral, which produce multiple concentric cones. These cones form 2 to 3 bands of relatively coarse droplets, surrounded by wider bands of relatively fine droplets.

The large surface area of spray improves evaporation and cooling.

Available Spray Angles
90 - 120°
Flow Rate Range
3 to 597 gpm
Available Connection Types
  • Pipe: 1/2, 1, 1 1/2
  • Connection Methods: Thread (NPT, BSP, Male)
Materials
Brass, 316, Nickel Aluminum Bronze, Titanium
Flow Rates, Spray Angles, Connections
Full Cone
Select a nozzle number below for performance graph, drawings, and to request a quote.
Flow rate (gpm/lpm) is calculated at differential pressure (psi/bar).
Nozzle Number
Connection Sizes
Spray Angles
Flow Rate (gpm) @ Differential Pressure (psi) (Density: 1 SG)
10 psi
20 psi
50 psi
75 psi
100 psi
150 psi
Pipe: 1/2
90°, 120°
3.00
4.24
6.71
8.22
9.49
11.6
Pipe: 1/2
90°, 120°
5.31
7.51
11.9
14.5
16.8
20.6
Pipe: 1/2
90°, 120°
8.25
11.7
18.5
22.6
26.1
32.0
Pipe: 1/2
90°, 120°
12.0
17.0
26.9
33.0
38.1
46.7
Pipe: 1/2
90°, 120°
16.5
23.3
36.9
45.2
52.2
63.9
Pipe: 1/2, 1
90°, 120°
21.0
29.7
47.0
57.5
66.4
81.3
Pipe: 1
90°, 120°
33.5
47.4
75.0
91.8
106
130
Pipe: 1 1/2
90°, 120°
47.4
67.1
106
130
150
184
Pipe: 1 1/2
90°, 120°
64.5
91.2
144
177
204
250
Pipe: 1 1/2
90°, 120°
84.4
119
189
231
267
327